Model:
Specification:1.5kW-630kW
Introduction:
AC input reactor can effectively eliminate the high-order harmonics on the input side and prevent other equipment from being damaged due to voltage waveform distortion; at the same time, it can also improve the power factor on the input side of the inverter.
(1) Working voltage: 220VAC-1140VAC
(2) Working frequency: 50/60Hz.
(3) Working current: 3A-1600A a
(4) Insulation class: class F,H
(5) Use environment: -10~+45 ℃, the rated value will not be reduced. Up to +55°C at , above 45°C, the rated current decreases by 2% for every 1°C increase
(6) Protection class: IP00-IP22
(7) Pressure drop:<4% greater than this range will cause torque loss
(8) Maximum current: 1.5× rated current for 60S
(9) Noise sound: ≤65dB
(10) Temperature liter:≤85K
(11) Dielectric strength: iron core-winding 3000VAC/50Hz/5mA/10s without arcing breakdown (factory test)
(12) Insulation resistance: 1000VDC insulation resistance ≥100MΩ
(13) The altitude does not exceed 2000 meters.
(14) The operating ambient temperature is -25℃~+45℃, and the relative humidity does not exceed 90%.
(15) There is no harmful gas or flammable and explosive materials around.
(16) The surrounding environment should have good ventilation conditions. If it is installed in a cabinet, ventilation equipment should be installed.
(17) Executive standards: IEC289:1987 reactor, GB10229-88 reactor (eqvIEC289:1987), JB9644-1999 reactor for semiconductor electrical transmission